Location: Home >> Products >> Industrial Ethernet >> Remote I/O >> Active Ethernet I/O >> ioLogik E2260

ioLogik E2260

Active Ethernet I/O with 6 RTD inputs and 4 digital outputs

Datasheet
Manual
Drivers & Software
Larger image
 


Features
Specifications
Ordering Information

Features and Benefits


  1. Supports PT, JPT, Ni RTD sensor types and resistors
  2. Adjustable RTD sampling rate
  3. Instant event messaging by TCP/UDP/e-mail/SNMP trap
  4. PC-based configuration utility and web console
  5. Easy-to-use Click&Go™ Logic for local output control
  6. Windows/WinCE VB/VC and Linux C API
  7. I/O control over Modbus/TCP and SNMP protocol
  8. NIST traceable calibration

     

Introduction


Bring intelligence to temperature measurement

The ioLogik E2260 brings intelligence to temperature sensors. It comes equipped with virtual channels that are designed to calculate the average value of each channel, and the difference between two channels. And it does all this without a controller or PC.



Compatible with popular RTD temperature sensors

The ioLogik E2260 offers PT100, PT1000, JPT, and Ni sensor types and a resistor of up to 2.2 Kohms, and supports using your own resistance sensor, such as PTC or NTC for your HVAC applications.


More info >>

•  LAN:
Ethernet10/100Mbps, RJ45
Protection1.5KV magnetic isolation
ProtocolsModbus/TCP, TCP/IP, UDP, DHCP, Bootp, SNMP(MIB for I/O and Network), HTTP, SNTP


•  Serial:
InterfaceRS-485-2w: Data+, Data-, GND
Serial Line Protection15KV ESD for all signals


•  Serial Communication Parameters:
Data Bits8
Stop Bits1
ParityNone
Flow ControlNone
ProtocolsModbus/RTU
Speed1200 to 115200 bps


•  RTD:
Channels6, RTD channels
Sampling Rate12 samples/sec (all channels)
Resolution0.1˚C or 0.1 ohms
Accuracy± 0.1% FSR @ 25˚C
±0.3% FSR @ -10 and 60˚C
Input Impedence625K ohms(min.)
Input TypePt, JPt, Ni, RTD sensors, resister


•  Digital Output:
Channels4, sink, 45 VDC, 200 mA
Optical Isolation Protection3K VDC or 2K Vrms
Output Frequency100 Hz
Over-voltage Protection45 VDC
Over-current Limit750 mA
Over-temperature Shutdown175˚C


•  Physical Characteristics:
WiringI/O cable max. 14AWG


•  Environmental Limits:
Operating Temperature-10 to 60°C (14 to 140°F)
Storage Temperature-40 to 85°C (-40 to 185°F)
Ambient Relative Humidity5 to 95% (non-condensing)


•  Power Requirements:
Input Voltage24 VDC nominal, 12 to 48 VDC
DO Power24 VDC nominal, up to 30 VDC


•  Agency Approvals:
EMIFCC Part 15, CISPR (EN55022) class A
EMSIEC 61000-4, IEC 61000-6
SafetyUL508
ShockIEC 60068-2-27
FreefallIEC 60068-2-32
VibrationIEC 60068-2-6


•  Warranty:
Warranty Period2 years
DetailsSee www.moxa.com/warranty



To request a quote, indicate which items you are interested in below and click "Get a Quote".
Active Ethernet I/O
 Model No. Descritpion

ioLogik E2260

Active Ethernet I/O with 6 RTD inputs and 4 digital outputs

LDP1602

LCD module with 16 x 2 text display and 5 buttons